Customization: | Available |
---|---|
Task: | Digita Output |
Structure: | Closed-Loop |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
SIMATIC DP, Electronics module for ET 200SP, F-DQ 4X24 V DC/2A, 15 mm width, up to PL E (ISO 13849) up to SIL 3 (IEC 61508) | |||
General information | |||
Product type designation | F-DQ 4x24 V DC/2A HF | ||
usable BaseUnits | BU type A0 | ||
Product function | |||
|
Yes; I&M0 to I&M3 | ||
Engineering with | |||
|
V12 | ||
|
V5.5 SP3 / - | ||
|
V2.31 | ||
Supply voltage | |||
Rated value (DC) | 24 V | ||
permissible range, lower limit (DC) | 20.4 V | ||
permissible range, upper limit (DC) | 28.8 V | ||
Reverse polarity protection | Yes | ||
power supply according to NEC Class 2 required | No | ||
Input current | |||
Current consumption (rated value) | 75 mA; without load | ||
Current consumption, max. | 21 mA; From the backplane bus | ||
output voltage / header | |||
Rated value (DC) | 24 V | ||
Power | |||
Power available from the backplane bus | 70 mW | ||
Power loss | |||
Power loss, typ. | 4 W | ||
Address area | |||
Address space per module | |||
|
5 byte | ||
|
5 byte | ||
Hardware configuration | |||
Automatic encoding
|
Yes | ||
Yes | |||
Digital outputs | |||
Type of digital output | Transistor | ||
Number of digital outputs | 4 | ||
Digital outputs, parameterizable | Yes | ||
Short-circuit protection
|
Yes | ||
> 3.3 A | |||
Open-circuit detection | Yes |
|
8 mA | ||
Overload protection
|
Yes | ||
2.9 A | |||
Limitation of inductive shutdown voltage to | Typ. -2x 47 V | ||
Switching capacity of the outputs | |||
|
2 A | ||
|
10 W | ||
Load resistance range | |||
|
12 ohm | ||
|
2 000 ohm | ||
Output voltage | |||
|
24 V; L+ (-0.5 V) | ||
Output current | |||
|
2 A | ||
|
0.5 mA | ||
Switching frequency | |||
|
30 Hz; Symmetrical | ||
|
0.1 Hz; according to IEC 60947-5-1, DC-13, symmetrical | ||
|
10 Hz; Symmetrical | ||
Total current of the outputs | |||
|
2 A; note derating data in the manual | ||
|
6 A; note derating data in the manual | ||
Cable length | |||
|
1 000 m | ||
|
500 m | ||
Interrupts/diagnostics/status information | |||
Diagnostics function | Yes | ||
Substitute values connectable | No | ||
Alarms | |||
|
Yes | ||
Diagnostics indication LED | |||
|
Yes; green LED | ||
|
Yes; red LED | ||
|
Yes; green PWR LED | ||
|
Yes; green LED | ||
|
Yes; red LED | ||
|
Yes; green/red DIAG LED | ||
Potential separation | |||
Potential separation channels | |||
|
No | ||
|
Yes | ||
|
No | ||
Isolation | |||
Isolation tested with | 707 V DC (type test) | ||
Standards, approvals, certificates | |||
Suitable for safety functions | Yes | ||
Highest safety class achievable in safety mode | |||
|
PLe | ||
|
SIL 3 | ||
Probability of failure (for service life of 20 years and repair time of 100 hours) | |||
- Low demand mode: PFDavg in accordance with SIL2 | < 2.00E-04 | ||
- Low demand mode: PFDavg in accordance with SIL3 | < 2.00E-05 | ||
- High demand/continuous mode: PFH in accordance with SIL2 | < 1.00E-08 1/h | ||
- High demand/continuous mode: PFH in accordance with SIL3 | < 1.00E-09 1/h | ||
Ambient conditions | |||
Ambient temperature during operation |
|
0 °C 60 °C 0 °C 50 °C |
Altitude during operation relating to sea level | |
|
4 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
Dimensions | |
Width | 15 mm 73 mm 58 mm |
Height | |
Depth | |
Weights | |
Weight, approx. | 57 g |