| Customization: | Available |
|---|---|
| Type: | Communication Coupler |
| Wiring Devices: | Other |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| Item | Specification | |
|---|---|---|
| Enclosure | Mounted in a panel | |
| Grounding method | Ground to 100 Ω or less | |
| Operating environment |
Ambient operating temperature |
0 to 55°C |
| Ambient operating humidity |
10% to 95% (with no condensation or icing) | |
| Atmosphere | Must be free from corrosive gases. | |
| Ambient storage temperature |
-25 to 70°C (with no condensation or icing) | |
| Altitude | 2,000 m max. | |
| Pollution degree | Pollution degree 2 or less: Meets IEC 61010-2-201. | |
| Noise immunity | Conforms to IEC61000-4-4. 2 kV (power supply line) | |
| Overvoltage category | Category II: Meets IEC 61010-2-201. | |
| EMC immunity level | Zone B | |
| Vibration resistance | Conforms to IEC 60068-2-6. 5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz, acceleration of 9.8 m/s2, 100 min each in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total) |
|
| Shock resistance | Conforms to IEC 60068-2-27. 147 m/s2, 3 times each in X, Y, and Z directions |
|
| Applicable standards * | cULus: Listed (UL 508 or UL61010-2-201), ANSI/ISA 12.12.01, EU: EN 61131-2, C-Tick or RCM, KC Registration, NK, and LR |
| Item | Specification | |||
|---|---|---|---|---|
| NX-ECC201 | NX-ECC202 | NX-ECC203 | ||
| Number of connectable NX Units | 63 Units max. *1 | |||
| Send/receive PDO data sizes | Input: 1,024 bytes max. (including input data, status, and unused areas) Output: 1,024 bytes max. (including output data and unused areas) |
|||
| Mailbox data size | Input: 256 bytes Output: 256 bytes |
|||
| Mailbox | Emergency messages and SDO requests | |||
| Refreshing methods *2 | • Free-Run refreshing • Synchronous I/O refreshing • Time stamp refreshing |
• Free-Run refreshing • Synchronous I/O refreshing • Time stamp refreshing • Task period prioritized refreshing |
||
| Node address setting range | When the settable node address range for the built-in EtherCAT port is 1 to 512 *3 • Set on switches: 1 to 199 • Set with the Sysmac Studio: 1 to 512 |
|||
| When the settable node address range for the built-in EtherCAT port is 1 to 192 *3 • Set on switches: 1 to 192 • Set with the Sysmac Studio: 1 to 192 |
||||
| I/O jitter performance | Inputs: 1 μs max. Outputs: 1 μs max. |
|||
| Communications cycle in DC Mode |
250 to 4,000 μs*4 *5 | 125 to 10,000 μs *3 *4 *6 | ||
| Unit power supply *7 |
Power supply voltage | 24 VDC (20.4 to 28.8 VDC) | ||
| NX Unit power supply capacity |
10 W max. Refer to Installation orientation and restrictions for details. |
|||
| NX Unit power supply efficiency |
70% | |||
| Isolation method | No isolation between NX Unit power supply and Unit power supply terminals | |||
| Current capacity of power supply terminals |
4 A max. | |||
| I/O power supply *7 |
Power supply voltage | 5 to 24 VDC (4.5 to 28.8 VDC) *8 | ||
| Maximum I/O power supply current |
4 A | 10 A | ||
| Current capacity of power supply terminals |
4 A max. | 10 A max. | ||
| NX Unit power consumption | 1.45 W max. | 1.25 W max. | ||
| Current consumption from I/O power supply |
10 mA max. (for 24 VDC) | |||
| Dielectric strength | 510 VAC for 1 min, leakage current: 5 mA max. (between isolated circuits) | |||
| Insulation resistance | 100 VDC, 20 MΩ min. (between isolated circuits) | |||
| External connection terminals | Communications Connector For EtherCAT communications. • RJ45 × 2 (shielded) • IN: EtherCAT input data, OUT: EtherCAT output data |
|||
| Screwless Clamping Terminal Block For Unit power supply, I/O power supply, and grounding. Removable. |
||||
| Peripheral USB Port For Sysmac Studio connection. • Physical layer: USB 2.0-compliant, B-type connector • Transmission distance: 5 m max. |
||||
| Dimensions | 46 × 100 × 71 mm (W×H×D) | |||
| Weight | 170 g max. | |||
| Installation orientation and restrictions |
Installation orientation: 6 possible orientations Restrictions: Used in the upright installation orientation. Used in another orientation other than the upright installation orientation. |
|||
| Circuit layout | ||||
| Terminal arrangement | ||||
| Accessory | End Cover (NX-END01): 1 | |||
| Shenzhen Aimiqu Technology Co., Ltd. |
Shenzhen Aimiqu Technology Co., Ltd. was established in 2016 and is located in Bao'an District, Shenzhen. The company has professional technical personnel, focusing on the development and practice of automation, digitalization, networking and intelligence in the industrial field. Provide products, solutions and services for the majority of industrial enterprises and governments with automation systems, digital factories, industrial Internet and industrial big data intelligent integration, and strive to become a domestic intelligent manufacturing overall solution provider. Shenzhen Aimiqu is a factory specializing in production & sales & research in electric cabinet. And Shenzhen Aimiqu is a specializing in sales original PLC&pneumatic products & Industrial Control Instrumentation including Siemens,Fairchild and ST etc and related accessories . In PLC&Pump Valve & Pneumatic industry&Industrial Control Instrumentation has a strong popularity and good reputation,and provide professional customized services(Our main business is according to customer dr... |