Customization: | Available |
---|---|
Task: | Program |
Structure: | Combination |
Still deciding? Get samples of US$ 300/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Terminal No. | Signal | Features |
---|---|---|
Digital inputs (DI) | ||
5 | DI0 | Digital inputs, isolated, 5.5 mA/24 V |
6 | DI1+ | Digital inputs, isolated, 5.5 mA/24 V |
64 | DI1- | Digital inputs, isolated, 5.5 mA/24 V |
7 | DI2 | Digital inputs, isolated, 5.5 mA/24 V |
8 | DI3+ | Digital inputs, isolated, 5.5 mA/24 V |
65 | DI3- | Digital inputs, isolated, 5.5 mA/24 V |
16 | DI4 | Digital inputs, isolated, 5.5 mA/24 V |
17 | DI5+ | Digital inputs, isolated, 5.5 mA/24 V |
66 | DI5- | Digital inputs, isolated, 5.5 mA/24 V |
67 | DI6 | Digital inputs, isolated, 5.5 mA/24 V |
69 | DI COM1 | Reference potential for digital inputs DI0, DI2, DI4, DI6 |
41 ... 44 | DI16 ... DI19 | Freely programmable (isolated) 5.5 mA/24 V |
40 | DI COM3 | Reference potential for digital inputs DI16 ... DI19 |
Digital inputs (DI) - Fail-safe (formed from two standard inputs using the appropriate parameter setting) |
||
5, 6 | F-DI0 | Fail-safe digital inputs, 2 channels (redundant), freely programmable (isolated) 5.5 mA/24 V |
7, 8 | F-DI1 | Fail-safe digital inputs, 2 channels (redundant), freely programmable (isolated) 5.5 mA/24 V |
16, 17 | F-DI2 | Fail-safe digital inputs, 2 channels (redundant), freely programmable (isolated) 5.5 mA/24 V |
69 | DI COM1 | Reference potential for digital inputs F-DI0, F-DI1, F-DI2 |
Switchable digital inputs or outputs (digital inputs DI24 to DI27 can also be used as a pulse input with a maximum frequency of 32 kHz) |
||
51 | DI24/DO24 | Freely programmable (not isolated), DI: 5.5 mA/24 V, DO: 100 mA/24 V |
53 | DI25/DO25 | Freely programmable (not isolated), DI: 5.5 mA/24 V, DO: 100 mA/24 V |
53 | DI26/DO26 | Freely programmable (not isolated), DI: 5.5 mA/24 V, DO: 100 mA/24 V |
54 | DI27/DO27 | Freely programmable (not isolated), DI: 5.5 mA/24 V, DO: 100 mA/24 V |
50 | GND | Reference potential |
Digital outputs (DO) | ||
18 | DO0, NC | Relay output DO0 NC contact (0.5 A, 30 V DC) |
19 | DO0, NO | Relay output DO0 NO contact (0.5 A, 30 V DC) |
20 | DO0, COM | Relay output DO0 Common contact (0.5 A, 30 V DC) |
21 | DO1 NO | Relay output DO1 NO contact (0.5 A, 30 V DC) |
22 | DO1 COM | Relay output DO1 Common contact (0.5 A, 30 V DC) |
23 | DO2, NC | Relay output DO2 NC contact (0.5 A, 30 V DC) |
24 | DO2, NO | Relay output DO2 NO contact (0.5 A, 30 V DC) |
25 | DO2, COM | Relay output DO2 Common contact (0.5 A, 30 V DC) |