Customization: | Available |
---|---|
After-sales Service: | One Year Warranty |
Principle: | Vibration Sensor |
Still deciding? Get samples of US$ 570/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
General | |
Manufacturer | Siemens |
Supplier | Siemens |
Product designation | Ultrasonic transducer |
Brand name | MultiRanger 100 |
Type designation | MultiRanger 100/200 Ultrasonic level controller: continuous, non-contact, 15 m (50 ft) range. Monitors level, volume, and open channel flow in liquids, slurries, and solids. |
Article number | 7ML50331BA101A |
Net weight | 1.4 kg |
Slogan | Single or dual point level monitor/controller |
Mode of operation and application | |
Measuring principle | ultrasonic |
Operating frequency of the transmitter | 44 kHz |
Input | |
Measurand | Level |
Number of sensor inputs | 2 |
Measuring range | |
Measuring range | 0.3 m ... 15 m |
Temperature compensation | -50 °C ... 150 °C |
Output | |
Current output | |
Number of outputs | 1 |
Signal range | 4 ... 20 mA |
0 ... 20 mA | |
Failure signal (minimum) | 3.8 mA |
Failure signal (maximum) | 22 mA |
Load, at active output (maximum) | 750 Ohm |
Digital output | |
Type | relais |
Relay output | |
Number | 3 |
Type 1 | Normally Open (NO) |
Number of outputs 1 | 2 |
Type 2 | Change-over (NO/NC) |
Number of outputs 2 | 1 |
Operating conditions | |
Degree of pollution | Pollution degree 4 |
Standard for the degree of pollution | IEC 61010-1 |
Overvoltage class | Installation category II |
Standard for the overvoltage class | IEC 61010-1 |
Environmental conditions | |
Ambient temperature during operation | -20 °C ... 50 °C |
Ambient temperature during storage | -20 °C ... 50 °C |
Degree of protection | |
IP rating | IP65 |
IP rating of the transmitter | IP65 |
NEMA Enclosure Type of the transmitter | NEMA 4X |
Electromagnetic compatibility EMC | |
Standard for EMC | EN 61326-1 |
Structural Design | |
Mechanical design | |
Design of the device | separated version, sensor separated |
Material | |
Enclosure | |
Material of the transmitter | Polycarbonate (PC) |
Cable entry & cable gland | |
Material of the cable entry | polyamide (PA) |
Mounting | |
Type of mounting | wall mounting |
Location | Indoor area |
Outdoor area | |
Electrical connections | |
Connection technology | 4-wire technology |
Potential insulation | galvanic |
Potential insulation | to all inputs |
to all outputs | |
to all supplies | |
to all communications interfaces | |
Number of cable entries | 4 |
Design of the cable entry | M20 x 1.5 |
Length of the connection cable | 365 m |
Display and operating controls | |
Display | with display |
Design of the display | LCD |
Power supply | |
Electrical | |
Voltage type | AC |
Nominal voltage, AC | 100 V |
230 V | |
Supply voltage, AC | 85 V ... 265 V |
Nominal frequency | 50 Hz |
60 Hz | |
Power consumption effective power | 17 W |
Power consumption apparent power | 36 VA |
Communication | |
Interface for communication | RS 485 |
Interface for programming | RJ11 jacket |
Protocol | MODBUS RTU |
Modbus ASCII | |
Programming | with infrared hand programmer |
SIMATIC PDM Software | |
Certificates and approvals | |
Verification of suitability | CE |
UL | |
CSA | |
C-Tick (RCM) | |
FM | |
Marine approval | Lloyd's Register of Shipping (LR) |
American Bureau of Shipping (ABS) | |
Environmental class according to Lloys´s Register approval system | ENV1 |
ENV2 | |
ENV3 | |
ENV5 | |
Reliability (MTBF) | |
MTBF | 62 a |
Standard for MTBF | SN 29500 |
Determination procedure | calculation with component load |
Reference temperature | 40 °C |
Applicability | Measuring device |