Customization: | Available |
---|---|
Phase: | Single Phase |
Type: | On-line |
Still deciding? Get samples of US$ 585/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The single-phase SITOP PSU8200 are technology power supplies for challenging solutions. The version with wide-range input allows a connection to almost any electricity supply network worldwide and ensures a high degree of safety even if there are large voltage fluctuations.
To further increase the 24 V availability, the SITOP power supplies can be combined with buffer, DC UPS, redundancy and selectivity modules.
SITOP PSU8200/1AC/24VDC/40A SITOP PSU8200 24 V/40 A stabilized power supply input: 120/230 V AC output: 24 V DC/40 A *Ex approval no longer available* |
|
Input | |
type of the power supply network | 1-phase and 2-phase AC |
supply voltage at AC | |
|
Automatic selection; startup starting from Ue ≥ 90/180 V |
supply voltage | |
|
120 V |
|
230 V |
input voltage | |
|
85 ... 132 V |
|
170 ... 264 V |
design of input wide range input | No |
operating condition of the mains buffering | at Vin = 230 V |
buffering time for rated value of the output current in the event of power failure minimum | 25 ms |
operating condition of the mains buffering | at Vin = 230 V |
line frequency | |
|
50 Hz |
|
60 Hz |
line frequency | 45 ... 65 Hz |
input current | |
|
15 A |
|
9 A |
current limitation of inrush current at 25 °C maximum | 50 A |
I2t value maximum | 8 A²·s |
fuse protection type | Yes |
|
Recommended miniature circuit breaker at 1-phase operation: 16 A characteristic C; required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2421-4BA10 (120 V) or 3RV2411- 1JA10 (230 V) |
Output | |
voltage curve at output | Controlled, isolated DC voltage 24 V |
output voltage at DC rated value | |
output voltage
|
24 V 3 % |
relative overall tolerance of the voltage | |
relative control precision of the output voltage
|
0.1 % 0.1 % |
residual ripple
|
100 mV |
|
50 mV |
voltage peak | |
|
240 mV |
|
220 mV |
adjustable output voltage | 24 ... 28 V |
product function output voltage adjustable | Yes |
type of output voltage setting | via potentiometer; max. 960 W |
display version for normal operation | Green LED for 24 V OK; LED yellow for overload; LED red for short- circuit or latching shutdown |
type of signal at output | Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK" |
behavior of the output voltage when switching on | Overshoot of Vout approx. 3 % |
response delay maximum | 1.5 s |
voltage increase time of the output voltage | |
|
30 ms |
output current | |
|
40 A |
|
0 ... 40 A; +60 ... +70 °C: Derating 3%/K |
supplied active power typical | 960 W |
short-term overload current | |
|
120 A |
|
120 A |
duration of overloading capability for excess current | |
|
25 ms |
|
25 ms |
constant overload current | |
|
60 A |
product feature | |
|
Yes; switchable characteristic |
number of parallel-switched equipment resources for increasing the power | 2 |
Efficiency | |
efficiency in percent | 92 % 82 W 6.8 W |
power loss [W]
|
|
Closed-loop control | |
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical | 1 % |
relative control precision of the output voltage load step of resistive load 50/100/50 % typical | 1.9 % |
setting time | |
|
2 ms |
|
2 ms |
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical | 3.8 % |
setting time | |
|
1 ms |
|
1 ms |
|
1 ms |
Protection and monitoring | |
design of the overvoltage protection | < 32 V 41 A Yes Alternatively, constant current characteristic approx. 41 A or latching shutdown 41 A 250% Iout rated up to 25 ms, 150% Iout rated up to 5 s/min LED yellow for "overload", LED red for "latching shutdown" or "short- circuit" |
response value current limitation typical | |
property of the output short-circuit proof | |
design of short-circuit protection | |
enduring short circuit current RMS value
|
|
overcurrent overload capability in normal operation | |
display version for overload and short circuit |
Safety | |
galvanic isolation between input and output | Yes Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 Class I 0.1 mA 0.1 mA IP20 |
galvanic isolation | |
operating resource protection class | |
leakage current
|
|
protection class IP | |
Approvals | |
certificate of suitability
|
Yes Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) No No No No No No Yes Yes Yes ABS, DNV GL Yes No Yes No No |
certificate of suitability
|
|
type of certification CB-certificate | |
certificate of suitability
|
|
certificate of suitability shipbuilding approval | |
shipbuilding approval | |
Marine classification association
|
|
EMC | |
standard
|
EN 55022 Class B - EN 61000-6-2 |
environmental conditions | |
ambient temperature
|
-25 ... +70 °C; with natural convection -40 ... +85 °C -40 ... +85 °C Climate class 3K3, 5 … 95% no condensation |
environmental category according to IEC 60721 | |
Mechanics | |
type of electrical connection
|
screw-type terminals L, N, PE: 1 screw terminal each for 0.2 ... 4 mm² single-core/finely stranded +, -: 2 screw terminals each for 0.5 ... 10 mm² 13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm² 145 mm 145 mm 150 mm 40 mm 40 mm 0 mm 0 mm 3.1 kg Yes |
width of the enclosure | |
height of the enclosure | |
depth of the enclosure | |
required spacing
|
|
net weight | |
product feature of the enclosure housing can be lined up |
fastening method | Snaps onto DIN rail EN 60715 35x15 Buffer module, redundancy module Device identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20 838 156 h Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
electrical accessories | |
mechanical accessories | |
MTBF at 40 °C | |
other information |