Rated current |
Ir |
≤ 46 mA |
Power dissipation |
|
≤ 900 mW |
Power consumption |
|
≤ 900 mW |
Input |
Connection side |
|
field side |
Connection |
|
terminals 1+, 2-; 3+, 4- |
Rated values |
|
acc. to EN 60947-5-6 (NAMUR) |
Open circuit voltage/short-circuit current |
|
approx. 8 V DC / approx. 8 mA |
Switching point/switching hysteresis |
|
1.2 ... 2.1 mA / approx. 0.2 mA |
Line fault detection |
|
breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA |
Pulse/Pause ratio |
|
min. 20 ms / min. 20 ms |
Output |
Connection side |
|
control side |
Connection |
|
terminals 5, 6; 7, 8 |
Output I |
|
signal ; relay |
Output II |
|
signal ; relay |
Contact loading |
|
250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 30 V DC/2 A resistive load |
Minimum switch current |
|
2 mA / 24 V DC |
Energized/De-energized delay |
|
≤ 20 ms / ≤ 20 ms |
Mechanical life |
|
107 switching cycles |
Transfer characteristics |
Switching frequency |
|
≤ 10 Hz |
Galvanic isolation |
Input/Output |
|
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Input/power supply |
|
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output/power supply |
|
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output/Output |
|
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Indicators/settings |
Display elements |
|
LEDs |
Control elements |
|
DIP switch |
Configuration |
|
via DIP switches |
Labeling |
|
space for labeling at the front |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2014/30/EU |
|
EN 61326-1:2013 (industrial locations) |
Low voltage |
|
|
Directive 2014/35/EU |
|
EN 61010-1:2010+A1:2019+A1:2019/AC:2019 |
Conformity |
Electromagnetic compatibility |
|
NE 21:2017 , EN 61326-3-1:2017 , EN IEC 61326-3-2:2018 |
Degree of protection |
|
IEC 60529:1989+A1:1999+A2:2013 |
Functional safety |
|
IEC/EN 61508:2010 |
Input |
|
EN 60947-5-6:2000 |
Ambient conditions |
Ambient temperature |
|
-40 ... 70 °C (-40 ... 158 °F) |
Mechanical specifications |
Degree of protection |
|
IP20 |
Connection |
|
screw terminals |
Mass |
|
approx. 100 g |
Dimensions |
|
12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2 |
Mounting |
|
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-type examination certificate |
|
BASEEFA 06 ATEX 0092 X |
Marking |
|
1 II 3(1)G Ex ec nC [ia Ga] IIC T4 Gc , 1 II (1)D [Ex ia Da] IIIC , 1 I (M1) [Ex ia Ma] I |