Customization: | Available |
---|---|
Task: | Program |
Structure: | Combination |
Still deciding? Get samples of US$ 275/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The modular SIMATIC S7-1200 Controller forms the core of our current range for basic but very precise automation tasks. The S7-1200 CPUs with Safety Integrated perform both standard and safety-oriented tasks.
5 Standard controllers with graded performances in different versions:
Characteristics |
CPU 1211C |
CPU 1212C |
CPU 1214C |
CPU 1215C |
CPU 1217C |
---|---|---|---|---|---|
Options |
DC/DC/DC, AC/DC/relay, DC/DC/relay |
DC/DC/DC, AC/DC/relay, DC/DC/relay |
DC/DC/DC, AC/DC/relay, DC/DC/relay |
DC/DC/DC, AC/DC/relay, DC/DC/relay |
DC/DC/DC |
Work memory, integrated |
50 KB |
75 KB |
100 KB |
125 KB |
150 KB |
Load memory, integrated |
1 MB |
2 MB |
4 MB |
4 MB |
4 MB |
Memory card |
SIMATIC Memory Card (optional) |
||||
Digital inputs/outputs, integrated |
6/4 |
8/6 |
14/10 |
14/10 |
14/10 |
Analog inputs, integrated |
2 |
2 |
2 |
2 |
2 |
Analog outputs, integrated |
0 |
0 |
0 |
2 |
2 |
Process image |
1024 bytes for inputs, 1024 bytes for outputs |
||||
Expansion by signal board |
Max. 1 |
Max. 1 |
Max. 1 |
Max. 1 |
Max. 1 |
Expansion by signal modules |
No |
Max. 2 |
Max. 8 |
Max. 8 |
Max. 8 |
Expansion by communications modules |
Max. 3 |
Max. 3 |
Max. 3 |
Max. 3 |
Max. 3 |
Application
S7-1200 - CPU 1211C
For introduction to the Basic Controller family
S7-1200 - CPU 1212C
More memory, more integrated IOs and more expansion possibilities as compared to CPU 1211C
S7-1200 - CPU 1214C
More memory, more integrated IOs as compared to CPU 1212C and maximum expansion possibilities
S7-1200 - CPU 1215C
More memory, an additional Ethernet port and integrated analog outputs
as compared to CPU 1214C
S7-1200 - CPU 1217C
More memory, faster counters than CPU 1215C
SIMATIC S7-1200, CPU 1212C, compact CPU, DC/DC/relay, onboard I/O: 8 DI 24 V DC; 6 DO relay 2 A; 2 AI 0-10 V DC, Power supply: DC 20.4- 28.8V DC, Program/data memory 75 KB | |
General information | |
Product type designation | CPU 1212C DC/DC/relay V4.5 |
Firmware version | |
Engineering with | |
|
STEP 7 V17 or higher |
Supply voltage | |
Rated value (DC)
|
Yes 20.4 V 28.8 V Yes |
permissible range, lower limit (DC) | |
permissible range, upper limit (DC) | |
Reverse polarity protection | |
Load voltage L+ | |
|
24 V 20.4 V 28.8 V |
Input current | |
Current consumption (rated value) | 400 mA; CPU only 1 200 mA; CPU with all expansion modules 12 A; at 28.8 V 0.8 A²·s |
Current consumption, max. | |
Inrush current, max. | |
I²t | |
Output current | |
for backplane bus (5 V DC), max. | 1 000 mA; Max. 5 V DC for SM and CM |
Encoder supply | |
24 V encoder supply | |
|
L+ minus 4 V DC min. |
Power loss | |
Power loss, typ. | 9 W |
Memory | |
Work memory | |
|
75 kbyte No |
Load memory | |
|
2 Mbyte with SIMATIC memory card |
Backup | |
|
Yes Yes Yes |
CPU processing times | |
for bit operations, typ. | 0.08 µs; / instruction 1.7 µs; / instruction 2.3 µs; / instruction |
for word operations, typ. | |
for floating point arithmetic, typ. | |
CPU-blocks | |
Number of blocks (total) | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used |
OB | |
|
Limited only by RAM for code |
Data areas and their retentivity | |
Retentive data area (incl. timers, counters, flags), max. | 14 kbyte |
Flag | |
|
4 kbyte; Size of bit memory address area |
Local data | |
|
16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB |
Address area | |
Process image | |
|
1 kbyte 1 kbyte |
Hardware configuration | |
Number of modules per system, max. | 3 comm. modules, 1 signal board, 2 signal modules |
Time of day | |
Clock | |
|
Yes 480 h; Typical ±60 s/month at 25 °C |
Digital inputs | |
Number of digital inputs
|
8; Integrated 6; HSC (High Speed Counting) Yes |
Source/sink input | |
Number of simultaneously controllable inputs | |
all mounting positions | |
- up to 40 °C, max. | 8 |
Input voltage | |
|
24 V 5 V DC at 1 mA 15 V DC at 2.5 mA |
Input delay (for rated value of input voltage) | |
for standard inputs | |
- parameterizable - at "0" to "1", min. - at "0" to "1", max. |
0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four 0.2 ms 12.8 ms |
for interrupt inputs | |
- parameterizable | Yes |
for technological functions | |
- parameterizable | Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz |
Cable length | |
|
500 m; 50 m for technological functions 300 m; for technological functions: No |
Digital outputs | |
Number of digital outputs | 6; Relays |
Switching capacity of the outputs | |
|
2 A 30 W with DC, 200 W with AC |
Output delay with resistive load | |
|
10 ms; max. |
|
10 ms; max. |
Relay outputs | |
|
6 mechanically 10 million, at rated load voltage 100 000 |
Cable length | |
|
500 m 150 m |
Analog inputs | |
Number of analog inputs | 2 |
Input ranges | |
|
Yes |
Input ranges (rated values), voltages | |
|
Yes ≥100k ohms |
Cable length | |
|
100 m; twisted and shielded |
Analog outputs | |
Number of analog outputs | 0 |
Analog value generation for the inputs | |
Integration and conversion time/resolution per channel | |
|
10 bit Yes 625 µs |
Encoder | |
Connectable encoders | |
|
Yes |
1. Interface | |
Interface type | PROFINET |
Isolated | Yes |
automatic detection of transmission rate | Yes |
Autonegotiation | Yes |
Autocrossing | Yes |
Interface types | |
|
Yes 1 No |
Protocols | |
|
Yes |
|
Yes |
|
Yes |
|
Yes; Optionally also encrypted |
|
Yes |
|
No |
PROFINET IO Controller | |
|
100 Mbit/s |
Services | |
- PG/OP communication | Yes; encryption with TLS V1.3 pre-selected |
- Isochronous mode | No |
- IRT | No |
- PROFIenergy | No |
- Prioritized startup | Yes |
- Number of IO devices with prioritized startup, | 16 |
max. | |
- Number of connectable IO Devices, max. | 16 |
- Number of connectable IO Devices for RT, | 16 |
max. | |
- of which in line, max. | 16 |
- Activation/deactivation of IO Devices | Yes |
- Number of IO Devices that can be | 8 |
simultaneously activated/deactivated, max. |
- Updating time | The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. |
PROFINET IO Device | |
Services | |
- PG/OP communication | Yes; encryption with TLS V1.3 pre-selected |
- Isochronous mode | No |
- IRT | No |
- PROFIenergy | Yes |
- Shared device | Yes |
- Number of IO Controllers with shared device, max. | 2 |
Protocols | |
Supports protocol for PROFINET IO | Yes No Yes; CM 1243-5 (master) or CM 1242-5 (slave) required Yes; OPC UA Server Yes; CM 1243-2 required |
PROFIsafe | |
PROFIBUS | |
OPC UA | |
AS-Interface | |
Protocols (Ethernet) | |
|
Yes |
|
No |
|
Yes |
|
Yes |
|
Yes |
Redundancy mode | |
Media redundancy | |
|
No No |
SIMATIC communication | |
|
Yes |
Open IE communication | |
|
Yes |
- Data length, max. | 8 kbyte |
|
Yes |
- Data length, max. | 8 kbyte |
|
Yes |
- Data length, max. | 1 472 byte |
Web server | |
|
Yes Yes |
OPC UA | |
|
Yes; "Basic" license required |
|
Yes; data access (read, write, subscribe), method call, runtime license |
required | |
- Application authentication | Available security policies: None, Basic128Rsa15, Basic256Rsa15, |
Basic256Sha256 | |
- User authentication | "anonymous" or by user name & password |
- Number of sessions, max. | 10 |
- Number of subscriptions per session, max. | 5 |
- Sampling interval, min. | 100 ms |
- Publishing interval, min. | 200 ms |
- Number of server methods, max. | 20 |
- Number of monitored items, max. | 1 000 |
- Number of server interfaces, max. | 2 |
- Number of nodes for user-defined server | 2 000 |
interfaces, max. | |
Further protocols | |
|
Yes |
communication functions / header | |
S7 communication | |
|
Yes |