SIMATIC DP, POWER M. F-PM-E PPM PROFIsafe, for ET 200SP; 24 V DC safe shutdown of DQ and F-DQ up to PL D/SIL2 or PL E/SIL3 2 for safe dig. inputs 1 for safe dig. output PPM |
|||
General information | |||
Product type designation | F-PM-E 24 V DC/8 A PPM ST | ||
usable BaseUnits | BU type C0 | ||
Color code for module-specific color identification plate | CC52 | ||
Product function | |||
|
Yes; I&M0 to I&M3 | ||
Engineering with | |||
|
V12 | ||
|
V5.5 SP3 / - | ||
|
V2.31 | ||
Supply voltage | |||
Rated value (DC) | 24 V | ||
permissible range, lower limit (DC) | 20.4 V | ||
permissible range, upper limit (DC) | 28.8 V | ||
Reverse polarity protection | Yes | ||
Input current | |||
Current consumption (rated value) | 75 mA; without load | ||
Current consumption, max. | 21 mA; From the backplane bus | ||
output voltage / header | |||
Rated value (DC) | 24 V | ||
Encoder supply | |||
Number of outputs | 2 | ||
Short-circuit protection | Yes; Electronic (response threshold 0.7 A to 2.1 A) | ||
Output current | |||
|
0.3 A | ||
24 V encoder supply | |||
|
Yes; min. L+ (-1.5 V) | ||
|
Yes | ||
|
600 mA; Total current of all encoders | ||
Power | |||
Power available from the backplane bus | 70 mW | ||
Power loss | |||
Power loss, typ. | 5 W | ||
Address area | |||
Address space per module | |||
|
7 byte | ||
|
5 byte | ||
Hardware configuration |
Automatic encoding
|
Yes Yes |
Digital inputs | |
Number of digital inputs | 2 Yes; P-reading Yes |
Source/sink input | |
Input characteristic curve in accordance with IEC 61131, type 1 | |
Input voltage | |
|
DC 24 V -30 to +5 V +15 to +30 V |
Input current | |
|
3.7 mA |
Input delay (for rated value of input voltage) | |
for standard inputs | |
- parameterizable - at "0" to "1", min. - at "0" to "1", max. - at "1" to "0", min. - at "1" to "0", max. |
Yes 0.4 ms 20 ms 0.4 ms 20 ms |
for technological functions | |
- parameterizable | No |
Cable length | |
|
1 000 m 500 m |
Digital outputs | |
Number of digital outputs | 1 Yes > 14.8 A Yes 8 mA Yes 8.8 A Max. -1.5 V |
Short-circuit protection
|
|
Open-circuit detection
|
|
Overload protection
|
|
Limitation of inductive shutdown voltage to | |
Switching capacity of the outputs | |
|
8 A 100 W |
Load resistance range | |
|
3 ohm 2 000 ohm |
Output voltage | |
|
24 V; L+ (-0.5 V) |
Output current | |
|
8 A 1.5 mA; PP-switching: max. 1.5 mA; PM-switching: max. 1 mA |
Switching frequency | |
|
10 Hz; Symmetrical 0.1 Hz; according to IEC 60947-5-1, DC-13, symmetrical 4 Hz; Symmetrical |
Total current of the outputs | |
|
8 A; note derating data in the manual 8 A; note derating data in the manual |
Cable length | |
|
1 000 m 500 m |
Interrupts/diagnostics/status information | |
Diagnostics function | Yes; See Chapter "Alarms/diagnostic messages" in the manual No |
Substitute values connectable | |
Alarms |
|
Yes No |
Diagnostics indication LED | |
|
Yes; green LED Yes; red LED Yes; green PWR LED Yes; green LED Yes; red LED Yes; green/red DIAG LED |
Potential separation | |
Potential separation channels | |
|
No Yes No |
Isolation | |
Isolation tested with | 707 V DC (type test) |
Standards, approvals, certificates | |
Suitable for safety functions | Yes |
Highest safety class achievable in safety mode | |
|
PLe SIL 3 |
Ambient conditions | |
Ambient temperature during operation | |
|
0 °C 60 °C 0 °C 50 °C |
Dimensions | |
Width | 20 mm 73 mm 55 mm |
Height | |
Depth | |
Weights | |
Weight, approx. | 70 g |