Phase: | Single Phase |
---|---|
Type: | On-line |
Protection: | The Overvoltage Protection,Short-Circuit Protectio |
Application: | Industry |
Classification: | Lighting/Power |
Standby Time: | Long-acting Machine |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
The single-phase SITOP PSU8200 are technology power supplies for challenging solutions. The version with wide-range input allows a connection to almost any electricity supply network worldwide and ensures a high degree of safety even if there are large voltage fluctuations.
To further increase the 24 V availability, the SITOP power supplies can be combined with buffer, DC UPS, redundancy and selectivity modules.
Input | |
type of the power supply network | 3-phase AC |
supply voltage at AC | |
|
400 V |
|
500 V |
|
340 V |
|
550 V |
design of input wide range input | Yes |
operating condition of the mains buffering | at Vin = 400 V |
buffering time for rated value of the output current in the event of power failure minimum | 6 ms |
operating condition of the mains buffering | at Vin = 400 V |
line frequency | |
|
50 Hz |
|
60 Hz |
line frequency | 47 ... 63 Hz |
input current | |
|
2 A |
|
1.7 A |
current limitation of inrush current at 25 °C maximum | 60 A |
I2t value maximum | 3.4 A²·s |
fuse protection type | none |
|
Required: 3-pole connected miniature circuit breaker 10 ... 16 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489-listed, DIVQ) |
Output | |
voltage curve at output | Controlled, isolated DC voltage |
output voltage at DC rated value | 24 V |
output voltage | |
|
24 V |
relative overall tolerance of the voltage | 3 % |
relative control precision of the output voltage | |
|
1 % |
|
2 % |
residual ripple | |
|
150 mV |
voltage peak | |
|
240 mV |
adjustable output voltage | 24 ... 28 V |
product function output voltage adjustable | Yes |
type of output voltage setting | via potentiometer; max. 960 W |
display version for normal operation | Green LED for 24 V OK |
type of signal at output | Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK" |
behavior of the output voltage when switching on | No overshoot of Vout (soft start) |
response delay maximum | 1.5 s |
voltage increase time of the output voltage | |
|
15 ms |
|
500 ms |
output current | |
|
40 A |
|
0 ... 40 A; 48 A up to +45°C; +60 ... +70 °C: Derating 3%/K |
supplied active power typical | 960 W |
short-term overload current | |
|
65 A |
|
65 A |
duration of overloading capability for excess current | |
|
100 ms |
|
100 ms |
product feature | |
|
Yes |
number of parallel-switched equipment resources for increasing the power | 2 |
Efficiency | |
efficiency in percent | 91.5 % |
power loss [W] | |
|
89 W |
current typical | |
Closed-loop control | |
relative control precision of the output voltage with rapid | 3 % |
fluctuation of the input voltage by +/- 15% typical | |
relative control precision of the output voltage load step of | 1.5 % |
resistive load 50/100/50 % typical | |
setting time | |
|
1 ms |
|
1 ms |
relative control precision of the output voltage at load step | 3 % |
of resistive load 10/90/10 % typical | |
setting time | |
|
1 ms |
|
1 ms |
|
10 ms |
Protection and monitoring | |
design of the overvoltage protection response value current limitation typical property of the output short-circuit proof design of short-circuit protection enduring short circuit current RMS value
|
protection against overvoltage in case of internal fault Vout < 35 V 50 A Yes Electronic shutdown, automatic restart 14 A overload capability 150 % Iout rated up to 5 s/min |
Safety | |
galvanic isolation between input and output | Yes |
galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178, transformer acc. to EN 61558-2-16 |
operating resource protection class | Class I |
protection class IP | IP20 |
Approvals | |
certificate of suitability | |
|
Yes |
|
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) |
|
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) |
|
No |
|
No |
certificate of suitability | |
|
No |
Marine classification association
|
No No No Yes Yes Yes ABS, DNV GL Yes No Yes No No |
EMC | |
standard | |
|
EN 55022 Class B |
|
EN 61000-3-2 |
|
EN 61000-6-2 |
environmental conditions | |
ambient temperature | |
|
-25 ... +70 °C; with natural convection |
|
-40 ... +85 °C |
|
-40 ... +85 °C |
environmental category according to IEC 60721 | Climate class 3K3, 5 … 95% no condensation |
Mechanics | |
type of electrical connection | screw-type terminals |
|
L1, L2, L3, PE: 1 screw terminal each for 0.5 ... 4 mm² single-core/finely stranded |
|
+, -: 2 screw terminals each for 0.5 ... 10 mm² |
|
13, 14 (alarm signal): 1 screw terminal each for 0.05 2.5 mm² |
width of the enclosure | 145 mm |
height of the enclosure | 145 mm |
depth of the enclosure | 150 mm |
required spacing | |
|
40 mm |
|
40 mm |
|
0 mm |
|
0 mm |
net weight | 3.1 kg |
product feature of the enclosure housing can be lined up | Yes |
fastening method | Snaps onto DIN rail EN 60715 35x15 |
electrical accessories | Redundancy module, buffer module, selectivity module, DC UPS |
mechanical accessories | Device identification label 20 mm × 7 mm, pale turquoise 3RT1900- 1SB20 |
MTBF at 40 °C | 500 000 h |
other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
Suppliers with verified business licenses