Customization: | Available |
---|---|
Task: | Following |
Function: | Digital Output |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
General information | |
Product type designation | DQ 8x230 V AC/5 A ST (relay) |
HW functional status | From FS02 |
Firmware version | V2.1.0 |
|
Yes |
|
Yes No No No Yes Yes; FW V2.1.0 or higher |
Supply voltage | |
Rated value (DC) permissible range, lower limit (DC) permissible range, upper limit (DC) Reverse polarity protection |
24 V 19.2 V 28.8 V Yes |
Input current | |
Current consumption, max. | 80 mA |
output voltage / header | |
Rated value (AC) | 230 V; 24 V DC to 120 V DC / 24 V AC to 230 V AC |
Power | |
Power available from the backplane bus | 0.8 W |
Power loss | |
Power loss, typ. | 5 W |
Digital outputs | |
Type of digital output Number of digital outputs Current-sinking |
Relays 8 Yes |
Current-sourcing Digital outputs, parameterizable Short-circuit protection Controlling a digital input Size of motor starters according to NEMA, max. |
Yes Yes No Yes; possible 5 |
Switching capacity of the outputs | |
|
1 500 W; 10 000 operating cycles 10x 58 W (25 000 operating cycles) 1x 58 W (25 000 operating cycles) 10x 58 W (25 000 operating cycles) |
Output current | |
|
5 A 5 mA; 10 V 8 A; thermal continuous current 0 A |
Parallel switching of two outputs | |
|
Yes No Yes |
Switching frequency | |
|
2 Hz 0.5 Hz 2 Hz |
Total current of the outputs | |
|
8 A; see additional description in the manual 8 A; see additional description in the manual 64 A; see additional description in the manual |
Relay outputs | |
|
8 24 V 80 mA With miniature circuit breaker with characteristic B for: cos φ 1.0: 600 A cos φ 0.5 0.7: 900 A with 8 A Diazed fuse: 1 000 A No 4 000 000; see additional description in the manual Yes; 250 V AC/5 A g.p.; 120 V AC TV-4 tungsten; A300, R300 |
Switching capacity of contacts | |
|
see additional description in the manual see additional description in the manual |
Cable length | |
|
1 000 m 600 m |
Interrupts/diagnostics/status information | |
Diagnostics function Substitute values connectable |
Yes Yes |
Alarms |
|
Yes; green LED Yes; red LED Yes; Yellow LED Yes; green LED Yes; green LED No Yes; red LED |
Potential separation | |
Potential separation channels |
|
1 Yes Yes |
Permissible potential difference | |
between different circuits | 250 V AC between the channels and the supply voltage L+, 250 V AC between the channels and the backplane bus; 250 V AC between the channels (500 V AC when connecting different phases; basic insulation) |
Isolation | |
Isolation tested with | between the channels: 3 100 V DC; between the channels and the backplane bus: 3 100 V DC; between the channels and the supply voltage L+: 3 100 V DC; between the L+ and the backplane bus: 707 V DC (type test) |
Standards, approvals, certificates | |
Suitable for safety functions Suitable for safety-related tripping of standard modules |
No Yes; From FS03 |
|
PL c Cat. 2 |
Ambient conditions | |
Ambient temperature during operation | |
|
-30 °C; From FS03 60 °C -30 °C; From FS03 40 °C |
Dimensions | |
Width Height Depth |
35 mm 147 mm 129 mm |
Weights |
Weight, approx. 350 g