Task: | Collect |
---|---|
Structure: | Closed-Loop |
Mathematical Model: | Linear |
Signal: | Continuous |
Function: | Automatic Control, Monitoring, Measurement |
Certification: | CE |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
The SM 1231 RTD modules enable temperatures to be measured with high precision using established resistance temperature detectors.
The SM 1231 RTD modules exhibit the same structural features as the other modules of the S7-1200 series:
SIMATIC S7-1200, Analog input, SM 1231 RTD, 4xAI RTD module | |||
General information | |||
Product type designation | SM 1231, AI 4x16 bit RTD | ||
Supply voltage | |||
Rated value (DC) | 24 V | ||
Input current | |||
Current consumption, typ. | 40 mA | ||
from backplane bus 5 V DC, typ. | 80 mA | ||
Power loss | |||
Power loss, typ. | 1.5 W | ||
Analog inputs | |||
Number of analog inputs | 4; Resistance thermometer | ||
permissible input voltage for voltage input (destruction limit), max. | ±35 V | ||
Technical unit for temperature measurement adjustable | Degrees Celsius/degrees Fahrenheit | ||
Input ranges | |||
|
No | ||
|
No | ||
|
No | ||
|
Yes; Resistance-type transmitter: Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100, LG- Ni1000 | ||
|
Yes; 150 Ω, 300 Ω, 600 Ω | ||
Input ranges (rated values), resistance thermometer | |||
|
Yes | ||
10 ohm | |||
Yes | |||
100 ohm | |||
Yes | |||
1 000 ohm | |||
Yes | |||
1 000 ohm | |||
Yes | |||
120 ohm | |||
Yes | |||
200 ohm | |||
Yes | |||
500 ohm | |||
Yes | |||
100 ohm | |||
Yes |
- Input resistance (Pt 1000)
|
1 000 ohm Yes 200 ohm Yes 500 ohm |
||
Input ranges (rated values), resistors | |||
|
Yes Yes Yes |
||
Thermocouple (TC) | |||
Temperature compensation | |||
- parameterizable | No | ||
Analog value generation for the inputs | |||
Measurement principle | integrating | ||
Integration and conversion time/resolution per channel | |||
|
15 bit; + sign No 85 dB at 50 / 60 / 400 Hz |
||
Errors/accuracies | |||
Temperature error (relative to input range), (+/-) | 25 °C ±0.1%, to 55 °C ±0.2% total measurement range 0.05 % |
||
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | |||
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | |||
|
120 dB | ||
Interrupts/diagnostics/status information | |||
Alarms | Yes Yes; Can be read out |
||
Diagnostics function | |||
Alarms | |||
|
Yes | ||
Diagnoses | |||
|
Yes Yes |
||
Diagnostics indication LED | |||
|
Yes Yes |
||
Degree and class of protection | |||
IP degree of protection | IP20 | ||
Ambient conditions | |||
Free fall | |||
|
0.3 m; five times, in product package | ||
Ambient temperature during operation | |||
|
-20 °C 60 °C -20 °C 60 °C -20 °C 50 °C |
||
Ambient temperature during storage/transportation | |||
|
-40 °C 70 °C |
Air pressure acc. to IEC 60068-2-13 | |
|
795 hPa 1 080 hPa 660 hPa 1 080 hPa |
Relative humidity | |
|
95 % |
Pollutant concentrations | |
|
S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free |
connection method / header | |
required front connector | Yes |
Mechanics/material | |
Enclosure material (front)
|
Yes |
Dimensions | |
Width | 45 mm 100 mm 75 mm |
Height | |
Depth | |
Weights | |
Weight, approx. | 220 g |
Suppliers with verified business licenses